Maximum measurement error
Volume flow rate (standard): ±0.5% or ± 1 mm/s (0.04 in/s)
-
Measuring range
9 dm³/min to 282 m³/h (2.5 gal/min to 1250 gal/min)
-
Process temperature
Polyamide shell material: 0 to +60°C (+32 to +140°F)
-
Pressure field
PN 16, Class 150, 10K
-
Wetted Parts Materials
Polyamide coating material: 0 to +60°C (+32 to +140°F)
Electrodes: 1.4435 (316L)
Electromagnetic flow meter Proline Promag D10
Category: ENDRESS +HAUSER
The Promag D wafer flowmeter is designed for all basic water management applications where space is a problem. With its simple hardware and software design, Promag D 10 simplifies every phase of the life cycle, from development to maintenance, while ensuring the usual Endress+Hauser quality. Heartbeat Technology enables measurement reliability and verifies compliance